FEATURES



  • 5.7” touchscreen display with easy-to-read format, high level of controllability and customization (by both user and installer), Modbus communication, array of software features, and extensive diagnostic and troubleshooting functions.

  • Efficiencies of up to 98% steady state and 97% AFUE, and savings of up to 25%

  • Industry-leading modulation rates of up to 8:1

  • Can lead to a reduction of 2.5 tons of greenhouse gases, equivalent to two acres or 280 trees

  • Floor or wall-mount configuration

  • Factory-installed condensate trap with no moving parts

  • Spark ignition with dual electrodes using a high-output transformer

  • Removable door and hinged display panel for ultimate serviceability

  • No clearance required on the back, bottom or right side

  • Three configurable pump outputs

  • Integrated combustion platform (ICP)

    • Plug-In-Module card contains model specific information; can be used to upload/download custom settings

    • All operations are performed in one electronic controller

    • Sliding electrical box makes servicing easy

    • Critical components are independently fused for superior protection

    • Multiple inputs and outputs for ultimate controllability

    • Accepts modulation input from other energy management controllers

    • Quick connectors allow for easy diagnostics

    • High-capacity spark ignition generator

GENERAL SPECIFICATIONS:


























































  Lx150 Lx150E Lx200 Lx300* Lx400* Lx800*
Input Modulation (1000 btu/hr) 25-150 25-150 25-199 55-275 75-399 160-800
Water (NPT) 1** 1 1 1 1/4 1 1/4 2
Weight (lbs) 100 125 125 190 225 450
Max.  Pressure (PSI) 145*** 145 160 145 160
Gas Connection (NPT) 1/2 3/4 1
Vent & Air Size-Max. Length 3"-105' NG, 50' LP

4"/6"-100'****

Dimensions (H x W x D) 29.5x7x18.5" 36x17x21" 36x17x24" 37x17x53.5"


 


The Below Images Are a Before And after The Install of The NTI Trinity LX Series Boiler

Installed Unit Photo's: